Comparison of Heat Transfer in the Case of Turbulent Flow Between a Duct Without Ribs and a Duct with Semi-Circular Inner Ribs

Authors

  • Yamen Kbely Tishreen University

Keywords:

Heat transfer, Turbulent Flow, Duct, Inner Ribs.

Abstract

In this research, an experimental model was created to study the effect of adding a semi-circular internal rib inside a square-shaped duct on the heat transfer in case of turbulent flow, and a comparison was made between the air temperature inside the duct before and after adding the ribs.

Conditions studied: Reynolds numbers (10460- 40500), air temperature Inlet 25 ℃, the flow is manually changed by the flow control valve.

Through experiments, it was found that there was an improvement in the heat transfer of the duct equipped with circular ribs compared to the duct without a rib at a rate ranging between (10.87-28.13) %.

 

Author Biography

Yamen Kbely, Tishreen University

Master, Department of Power Mechanical, Faculty of  Mechanical and Electrical Engineering

Published

2021-07-07

How to Cite

1.
قبيلي ي. Comparison of Heat Transfer in the Case of Turbulent Flow Between a Duct Without Ribs and a Duct with Semi-Circular Inner Ribs. Tuj-eng [Internet]. 2021Jul.7 [cited 2024Dec.23];43(3). Available from: https://journal.tishreen.edu.sy/index.php/engscnc/article/view/10623